經(jīng)常有人咨詢到養(yǎng)殖場(chǎng)內(nèi)應(yīng)該用什么樣的發(fā)電機(jī)組,多大千瓦數(shù)的發(fā)電機(jī)組?可以根據(jù)自身的情況選擇發(fā)電機(jī)組,或者選擇普通發(fā)電機(jī)組。
People often ask what kind of generator set should be used in the breeding farm, and what is the kilowatt number of generator set? You can choose comler biogas generator set or common diesel generator set according to your own situation
一般養(yǎng)殖場(chǎng)內(nèi)的設(shè)備,分兩種,一種是水產(chǎn)養(yǎng)殖中供氧一類的設(shè)備,那種一般需要長(zhǎng)時(shí)間運(yùn)行的,另外一種就是想粉碎機(jī)等,每天用1-2個(gè)小時(shí),那種非常用的機(jī)器,比備用的使用時(shí)間長(zhǎng)。
Generally, there are two kinds of equipment in the aquaculture farm. One is the equipment for oxygen supply in aquaculture, which generally needs long-time operation. The other is the pulverizer, which is used for 1-2 hours a day. The very useful machine is longer than the standby one.
那么如何選擇準(zhǔn)確的發(fā)電機(jī)組,達(dá)到性價(jià)比高呢?
So how to choose an accurate generator set to achieve high cost performance ratio?
很多機(jī)器的啟動(dòng)電流都要大,一般是2-3倍,這就要求配比的發(fā)電機(jī)組時(shí),也要2倍以上甚至是3倍(水泵),比如一個(gè)12kw的粉碎機(jī),那么單獨(dú)配發(fā)電機(jī)組時(shí)就要2倍-2.5倍,那么就應(yīng)該選擇30kw的發(fā)電機(jī)組比較好!
The starting current of many machines is large, usually 2-3 times, which requires that the matching generator set should be more than 2 times or even 3 times (water pump). For example, a 12KW pulverizer needs 2 times - 2.5 times when the generator set is configured separately, so it is better to choose a 30kW generator set!
當(dāng)然這里的配比,不是所有機(jī)器負(fù)載的總和的2-3倍,這么說(shuō)吧,主要考慮負(fù)載前三位機(jī)器的負(fù)載。當(dāng)然這種情況指的是有人操作,可以一臺(tái)一臺(tái)啟動(dòng)機(jī)器的情況下。如果想要同時(shí)啟動(dòng),則好要2倍以上。
Of course, the ratio here is not 2-3 times of the total load of all machines. Let's put it this way, we mainly consider the load of the top three machines. Of course, this kind of situation refers to the situation that someone can start the machine one by one. If you want to start at the same time, it should be more than twice as good.
當(dāng)然作為銷售發(fā)電機(jī)組的廠家,結(jié)合我的銷售發(fā)電機(jī)組的經(jīng)驗(yàn),我并不推薦如此配比,因?yàn)樾詢r(jià)比不高。
Of course, as a manufacturer selling komler generator sets, combined with my experience in selling generator sets, I do not recommend such a ratio, because it is not cost-effective.
我推薦的配比是根據(jù)具體情況,分開(kāi)啟動(dòng),然后計(jì)算所需發(fā)電機(jī)組的kw數(shù)。
The ratio I recommend is to start separately according to the specific situation, and then calculate the kW of the required generator set.
例如:養(yǎng)殖場(chǎng)內(nèi)設(shè)備總負(fù)載53kw,其中大的幾個(gè)負(fù)載機(jī)器分別為24kw,12kw,7.5kw.剩余其他。
For example, the total load of the equipment in the farm is 53kw, of which the large load machines are 24kw, 12KW and 7.5kW respectively. The rest are others.
如果按照兩倍以上的配比的話,同時(shí)啟動(dòng)就需要120kw的發(fā)電機(jī)組才能啟動(dòng)正常運(yùn)行。
If the ratio is more than twice, it requires a 120kw generator set to start up and operate normally at the same time.
但實(shí)際上,并不需要同時(shí)啟動(dòng),像這個(gè)機(jī)器的話,可以單個(gè)啟動(dòng),先啟動(dòng)24kw的機(jī)器,再啟動(dòng)12kw的,后啟動(dòng)7.5kw的機(jī)器,大功率機(jī)器啟動(dòng)后,將剩余的全部啟動(dòng),這樣的話,機(jī)組配比功率為75kw,就足夠了。
However, in fact, it is not necessary to start the machine at the same time. For example, the machine can be started individually. First, the 24kw machine can be started, then the 12KW machine can be started, and then the 7.5kW machine can be started. After the high-power machine is started, all the remaining machines can be started. In this case, the matching power of the unit is 75kW, which is enough.
可能有些人不會(huì)算,這個(gè)簡(jiǎn)單,
Some people may not be able to calculate. This is simple,
75kw的發(fā)電機(jī)組,啟動(dòng)一臺(tái),需2-3倍電流,就是48kw,滿足,啟動(dòng)。
For a 75kW generator set, it needs 2-3 times of current to start, i.e. 48kW. Meet the requirements and start.
正常運(yùn)行后恢復(fù)正常,還剩51kw,然后再啟動(dòng)12kw的,需24kw,滿足,啟動(dòng),
After normal operation, return to normal, with 51kw remaining, and then start the 12KW, with 24kw required. If it is satisfied, start it,
正常運(yùn)行后恢復(fù)正常,還剩39kw,后再啟動(dòng)7.5kw的, 需15kw,滿足,啟動(dòng),
After normal operation, it will return to normal, with 39KW remaining. After that, if 7.5kW is started again, 15kw is required. If it is satisfied, it will be started,
正常運(yùn)行后恢復(fù)正常,還剩31.5kw,整個(gè)全部負(fù)載剩余9.5kw,也是可以啟動(dòng)的。
After normal operation, it will return to normal, with 31.5kw remaining and 9.5Kw remaining for the whole load. It can also be started.
所以上述所有電器全部啟動(dòng)完畢,當(dāng)然了,上述計(jì)算我是按照2倍電流計(jì)算的,實(shí)際情況可能按照2倍,2.5倍,或三倍的來(lái)計(jì)算。根據(jù)實(shí)際情況,來(lái)確定!
Therefore, all the above-mentioned electrical appliances have been started. Of course, the above calculation is based on twice the current. The actual situation may be based on twice, 2.5 times, or three times. Determine according to the actual situation!
The above is the detailed introduction of the natural gas generator set. I hope it will help you. If you have any questions, please contact us. We will provide you with services in a professional manner http://m.dgtmcnc.com