燃?xì)獍l(fā)電機(jī)組使用時(shí),進(jìn)行接線的時(shí)候有哪些要求,作為燃?xì)獍l(fā)電機(jī)廠家,讓小編帶大家共同了解一下燃?xì)獍l(fā)電機(jī)組使用時(shí)接線有哪些要求!
What are the requirements for wiring when using gas generator sets? As a gas generator manufacturer, let me take you to understand the wiring requirements when using gas generator sets!
1、為了人身安,發(fā)電機(jī)和開關(guān)屏須另接地線,地線面積不小于發(fā)電機(jī)輸出線截面積。地線可接在地下水管或深埋地下的鋼板上,保證接地良好,接地電阻不得大于50歐姆。
1. For personal safety, the generator and switch screen must be grounded separately, with a ground wire area not less than the cross-sectional area of the generator output line. The ground wire can be connected to underground water pipes or deep buried steel plates to ensure good grounding, and the grounding resistance should not exceed 50 ohms.
2、外殼是保護(hù)接地線,防止外殼帶電,中性點(diǎn)的線為工作中線,為4線制中線,一般大型機(jī)組要求接地電阻不大于4歐姆。
2. The shell is a protective grounding wire to prevent the shell from being electrified. The neutral wire is the working neutral wire, which is a 4-wire system neutral wire. Generally, large units require a grounding resistance of no more than 4 ohms.
3、移動(dòng)發(fā)電機(jī)工作零線要是不要用的話就不用接
3. If the working zero line of the mobile generator is not used, there is no need to connect it
4;要用的話接到配電箱里面去;保護(hù)零線在發(fā)電機(jī)附近打個(gè)樁就可以了。
4; If necessary, connect it to the distribution box; Just place a stake near the generator to protect the zero line.
、不管單相發(fā)電機(jī)還是三相發(fā)電機(jī),為了安全還是要接地的。漏電保護(hù)器一般情況下會(huì)起作用,但是都是有響應(yīng)時(shí)間的,所以保險(xiǎn)起見還是先接地。
Whether single-phase or three-phase generators, grounding is still necessary for safety reasons. Leakage protectors usually work, but they all have a response time, so for safety reasons, it is better to ground them first.
5、地線接線點(diǎn)安排在燃?xì)獍l(fā)電機(jī)組組的底盤末端,需接到合適的地線位置。
5. The grounding wire connection point is arranged at the end of the chassis of the gas generator set and needs to be connected to a suitable grounding wire position.
6、交流發(fā)電機(jī)接地中線的連接通常由用戶安裝時(shí)決定,當(dāng)燃?xì)獍l(fā)電機(jī)組組作為電源時(shí),中線須直接連到工廠接地線上。
6. The connection of the grounding neutral line of the AC generator is usually determined by the user during installation. When the gas generator set is used as the power source, the neutral line must be directly connected to the factory grounding wire.